Neutronic TT54B-G2

Reference 50023308

Description

Neutronic TT54B-G2 EA PPMS 4 supervised input loops

Alarm equipment category: PPMS, Dimensions (mm): 265 x 150 x 53 - white ABS V0, Protection rating: IP 40, Impact resistance: IK 07, Weight (with packaging): 800 g, Electric shock protection: class II, Power supply: 230 V, 50-60 Hz, Primary consumption: <10 mA, Batteries: Ni-MH - 600 mAh, Battery life: 30 hours on standby + 5 minutes in General Alarm, AMS alarm delay: 5 minutes to unlimited, Number of DS lines: 2, DS output power: 24 V - 500 mA for both lines, Length of the DS line: 1000 m with 2x2.5 mm² cable or 500 m with 2x1.5 mm² cable - Rfl = 2.2 kOhm, Number of DMs: no technical limit, Length of the DM line: 1000 m - Rfl = 1.0 kOhm, Dry contact alarm (x2): 0.25 A - 250 Vac or 1 A - 24 Vdc, Storage temperature: -20°C to +70°C, Operating temperature: -10°C to +55°C and operating RH: <95% without condensation.
Neutronic TT54B-G2

Neutronic TT54B-G2

Reference 50023308