Bosch FPP-5000-TI13 Communication interface Use with External Power Supply Unit Kit as communication interface between kit and panel (FPA‑5000/FPA-1200 EN54-13).
The FPP-5000-TI13 LSN Communication Interface is an extension for the FPP-5000
External Power Supply Unit Kit only. It is the communication interface between
the FPP-5000 and the panel, and transmits the following faults to the panel:
Mains fault; Battery fault; Battery internal resistance fault; BCM-0000-B
Battery Controller Module fault; Short 24 V outputs; Ground fault Additionally,
with the FSP-5000-RPS programming software, the switching outputs can be
programmed and the settings for the line monitoring according to EN 54-13 can
be done. The module is plugged next to the BCM-0000-B on the PRS-0002-C Panel
Rail Short and is power-supplied by the panel rail via the module bus (MOB).
The module’s front side shows 4 LEDs, which indicate the operation and fault
status.